DAD 141.1 Technical Manual Modbus Communication, Rev. 2.3 - Juni 2014 Page 9
This Index enables or disables the initial zero function @ power ON.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 221E.
see also command description: ZI Initial Zero ON/OFF
This Index selects the zero range.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 221E.
A value of 0 enables the standard zero range of ± 2% of maximum.
see also command description: ZR Zero Range
Store Tare value
@ Power OFF
This Index enables or disables the tare storing in EEPROM @ power OFF.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2224.
see also command description: TN Store Zero Value
Store Zero Value
@ Power OFF
This Index enables or disables the zero storing inh EEPROM @ power OFF.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2226.
see also command description: ZN Store Zero Value
This Index selects the trigger level.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2400.
see also command description: TL Trigger Level
This Index selects rising or falling slope trigger.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2402.
see also command description: TE Trigger Edge
This Index Reads/Modify the Hold time of setpoint S0.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2408.
see also command description: HT Hold Time
This Index Reads/Modify the tare window.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 240A.
see also command description: TW Tare Window
This Index Reads/Modify the tare time.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 240C.
see also command description: TI Tare Time
This Index Reads/Modify the time over which the average value will be built.
The 32 bit integer data accessed by reading or writing 2 16-bit registers from index 2410.
see also command description: MT Measure Time